Current transformer timing delay
How much time the current transformer itself costs, and with which sign. A CT gives lead, not delay, which is counter-intuitive: the lead you need from the inductor goes down by this amount rather than up. The site's phase-lead budget counted it as a plus until we worked this out.
I_burden = (I_pri/N) · jωL_m / (jωL_m + R) phase = 90° - arctan(ωL_m/R) = arctan( R / (ω·L_m) ) > 0 ⇒ LEAD t = φ / (360°·f) L_m2 = A_L2 · N₂² L_m1 = A_L1 · N₁² the first stage is loaded by the second's input, i.e. R/N₂², so its share is nil
Measure instead of computing where you can. Open the primary side of the second stage and measure the inductance of its secondary: that is L_m. The measured field takes priority over A_L.
Measuring the time directly is possible but needs a reference channel: a second CT with a high ratio and a low burden, so its own error is small, or a current clamp. Then compare its zeros against the voltage on the working burden. Going through L_m is more practical.
Only the magnetising term matters. The CT's leakage sits inside this same term rather than beside it. The signal is sensed across L1 + R, which puts the leakage upstream of the sense point and under 920 µH of L_m. Moving it from 0 to 1 µH shifts the total lead by 0.000085°. So this is the full figure, not a lower bound. The 13° quoted earlier belonged to a topology that is not on the board.
The wiring between the sense point and the burden is not included. It adds straight to L1: forgetting 0.3 µH of it at a 3.9 Ω burden turns a 55.5° lead into 59.4°, 7 % too much. See the current transformer page.